RBFM Handheld/Portable Clamp-on ultrasonic heat meters(BTU meters) employ the proven transit-time ultrasonic flow measurement technique combined with two PT 100 temperature sensors (or customer-supplied RTD sensors) for calculating total and instantaneous energy consumption. Flow measurement may be achieved via clamp-on, spool piece, or insertion-type sensors. Our microprocessor based, user friendly field programmable flow measurement technique creates no interruption of the process flow and allows for easy installation.
RBFM ultrasonic heat meter is available with a variety of features that make it adaptable to many different applications. Available transducer types include clamp-on, in-line, and insertion. Wall-mount, panel-mount, pipe-mounted and compact din-rail mounted display types are also offered. Additional available features include pulse, 0-20mA & 4-20mA outputs, RS-485communication, user-select-able engineering units, and a data logger function. This variety of features, combined with its low cost, make the RB series an ideal choice for economical BTU monitoring in many applications involving chillers, radiators, and heat exchanges.
RBFM Series Clamp-on transit time flow meter utilizes two transducers that function as both ultrasonic transmitters and receivers. The transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-method in which case the ultra sound transverses the pipe twice, or W-method in which case the ultra sound transverses the pipe four times, or in Z-method in which case the transducers are mounted on opposite sides of the pipe and the ultra sound transverses the pipe only once. The selection of mounting method depends on pipe and liquid characteristics. When the flow meter works, the two transducers transmits and receives ultrasonic signals amplified by multi beam which travels firstly downstream and then upstream (Figure 1). Because ultra sound travels faster downstream than upstream, there will be a difference of time of flight(△t). When the flow is still, the time difference(△t) is zero. Therefore, as long as we know the time of flight both downstream and upstream, we can work out the time difference, and then the flow velocity (V) and flow volume (Q) via the following formula.
V= K*D* △t
V: Liquid velocity
K: Constant
D: Distance between the two transducers
△t: Difference in time of flight
RBFM Handheld/Portable Clamp-on ultrasonic heat meters (BTU meters) Features
RBFM Handheld/Portable Clamp-on ultrasonic heat meters(BTU meters) Specification:
Transmitter |
Power Supply |
3 AAA Ni-H built-in batteries. When fully recharged it will last over 12 hours of operation. 90-240VAC for the charger |
||
Velocity |
0 ~ ±40 ft/s (0 ~±12m/s), bi-directional |
|||
Display |
2 line×10 English letters LCD back lit, can display total flow, flow rate, velocity and meter running status etc. |
|||
Units Rate Totalized |
User Configured (English and Metric); Rate and Velocity Display; (FWD, NET, REV or BATCH) gallons, ft³, barrels, lbs, liters, m³,kg |
|||
Output |
4-20mA; Pulse, Relay, RS485, options: up to 64 GB Data logger |
|||
Input |
3* 4-20mA 2*Pt100 3 wires can measure Heat |
|||
Accuracy |
±1.0%~2.0% of reading at rates >0.5 m/s |
|||
±2.0% of reading at rates <0.5 m/s |
||||
Sensitivity |
Flow Rate: 0.001ft/s (0.0003m/s) |
|||
Repeatability |
0.2% of reading |
|||
Security |
Keypad lockout, access code enable |
|||
Dimensions and Weight |
100×204×34 Weight: <0.6kg |
|||
Transducer |
Liquid Types Supported |
Virtually most any liquid containing less than 2% total suspended solids (TSS) or aeration |
||
Suited Liquid Temperature |
Std. Temp. Transducer: -40℃~160℃
|
|||
Dimensions and Weight |
S: Size:42×25×25; weight:<0.3kg M: Size:60×43×43; weight:<0.6kg L: Size:80×53×53; weight:<1.0kg |
|||
Temperature Sensor |
Pt100 |
|||
Pipe Size |
Transducer without Frame |
SN MN LN |
S transducer: DN15-100 Std M transducer: DN50-700 L transducer: DN300-6000 |
|
Transducer with Frame |
SPMN MPMN |
S transducer: DN15-100 Std M transducer: DN50-300 |
||
Data Logger |
Optional |
RBFM Ultrasonic Flow/Heat Meter Model Selection
RBFM |
X |
|
X |
X |
DNxx |
X |
X |
|
X |
X |
X |
|
|
Instrument Type |
|
||||||||||
F |
Ultrasonic Flowmeter |
|||||||||||
H |
Ultrasonic Heat meter |
|||||||||||
|
Power supply |
|||||||||||
A |
220VAC |
|||||||||||
D |
24VDC |
|||||||||||
B |
Battery |
|||||||||||
|
Flow/Heat meter Type |
|||||||||||
F |
Fixed type |
|||||||||||
H |
Handheld type |
|||||||||||
F |
Flanged type |
|||||||||||
B |
Battery type |
|||||||||||
|
|
|
|
Transducer Type |
||||||||
|
SN |
S type(pipe size: 15-100mm, temp.: -30 to 90℃) |
||||||||||
SH |
S type(pipe size: 15-100mm, temp.: -40 to 160℃) |
|||||||||||
SPMN |
S type with mounting frame only for Handheld (pipe size: 15-100mm, temp.: -40 to 90℃) |
|||||||||||
SPMH |
S type with mounting frame only for Handheld(pipe size: 15-100mm, temp.: -40 to 160℃) |
|||||||||||
MN |
M Type(pipe size: 50-700mm, temp.: -30 to 90℃)) |
|||||||||||
MH |
M Type(pipe size: 50-700mm, temp.: -40 to 160℃)) |
|||||||||||
MPMN |
M type with mounting frame only for Handheld (pipe size: 50-300mm, temp.: -40 to 90℃) |
|||||||||||
MPMH |
M type with mounting frame only for Handheld (pipe size: 50-300mm, temp.: -40 to 160℃) |
|||||||||||
RB-1 |
extended the mounting frame, for pipe:DN300-700mm, temp.: -40 to 90℃ |
|||||||||||
RBH |
extended the mounting frame, for pipe:DN300-700mm, temp.: -40 to 90℃ |
|||||||||||
LN |
L type(pipe size: 300-6000mm, temp.: -30 to 90℃) |
|||||||||||
LH |
L type(pipe size: 300-6000mm, temp.: -40 to 160℃) |
|||||||||||
I |
Insertion Type |
|||||||||||
IE |
Extended type |
|||||||||||
F |
Flanged type |
|||||||||||
|
Pt100 |
Temperature sensor |
||||||||||
|
DNxx |
Pipe size |
|
|||||||||
|
|
Pipe material |
|
|||||||||
|
C |
Carbon Steel |
||||||||||
SS |
Stainless Steel |
|||||||||||
CI |
cast iron |
|||||||||||
F |
Fibreglass |
|||||||||||
P |
PVC |
|||||||||||
C |
cement pipe |
|||||||||||
X |
Others, clarify |
|||||||||||
|
X |
Pressure(MPa) |
||||||||||
|
Output |
|||||||||||
N |
NO |
|||||||||||
A |
4-20mA |
|||||||||||
P |
Pulse |
|||||||||||
R |
Relay |
|||||||||||
2 |
RS232 |
|||||||||||
4 |
RS485 |
|||||||||||
5 |
Datalogger |
|||||||||||
|
Input |
|
||||||||||
N |
NO |
|||||||||||
1 |
1*4-20mA |
|||||||||||
2 |
2*4-20mA |
|||||||||||
3 |
3*4-20mA |
|||||||||||
|
Cable length |
|||||||||||
X |
meter |
Handheld Clamp-on Ultrasonic Heat meter(BTU meter) Applicants