Ultrasonic Flow Meter

The RBBF Ultrasonic Flow Meter is a fixed-mount, low cost transit-time ultrasonic flow meter with clamp-on transducers for non-invasive liquid flow rate measurement. Our microprocessor-based, user friendly field programmable creates no interruption of the process flow and has low installation costs.

This versatile series of flow meters is available in a variety of configurations. Available transducer types include clamp-on, in-line, and insertion. Wall-mount, panel-mount, pipe-mounted and compact din-rail mounted display types are also offered. Additional available features include pulse, 0-20mA & 4-20mA outputs, RS-232 communication, user-selectable engineering units, and a data logger function.

Description

  • Principle
  • Features
  • Specification
  • Model Selection
  • Applicants
  • Download
Principle

Features

RBBF Fixed  Clamp-on Type Ultrasonic Flow Meter Features:

  • Wide range velocities of ±0.1~ ± 12m/s (0.03 ~ ± 105 feet/sec.)
  • High accuracy of ± 1% of reading.
  • Transducers for pipe sizes ranging from13 to 6000 mm (½" to 240").
  • Fast response time - less than 1 second.
  • 2 line LCD display with flow rate, totalizer & signal condition.
  • Stores up 64 Day/months totalzier daily value.
  • Batch control function
  • Transducers for pipe sizes ranging from13 to 6000 mm (½" to 240").
  • 0-20mA & 4-20mA outputs, RS-232 communication, user-selectable engineering units, and a data logger function
  • Clamp-on transducers feature integral magnet for installation on metal pipe without use of a mounting belt
  • Data logger function includes date, totalizer, & signal condition diagnostic
Specification

RBBF Fixed Clamp-on Type Ultrasonic Flow Meter Features:

 

Transducer 

Standard Type   

S type

Pipe size

(15 mm ~ 100 mm) ½" ~ 4"

SN

SH

-30~160℃

Size(mm)

SN

45×25×28

M Type

Pipe size

50 mm ~ 700 mm (2" ~ 28" )

Temp.

MN

-30~160℃

Size(mm)

MN:

64×35×32

L Type

Pipe size

300~ 6000(12" ~ 240" )

Temp.

LN

-30~160℃

Size(mm)

LN

97×54×53

 

Insertion Type

Pipe size

80~6000mm

Temp.

RCN

-40 ~ 160℃

RCL(Extended)

-40 ~ 160℃

 

Temp. Sensor 

 

Pt100 3 wires 

 

Pt100 3 wires(only for small pipes)

Fluid

Water, sea water, industrial sewage, acid & alkali liquid, alcohol, beer, all kinds of oils which can transmit ultrasonic single uniform liquid

Flow Direction

Bi-directional measuring, net flow/heat measuring

Accuracy

± 1% ~ ± 2% of reading (1.5 ~ 100 feet/sec.)

Repeatability

± 0.2% of reading

Flow rate range

0.01 ~ ± 12 m/s

Response Time

Less than 1 second

Keypad

16 Key with tactile action

Pipe Material

Steel, stainless steel, cast iron, cement pipe, copper, PVC, aluminum, FRP etc. Liner is allowed

Liner Material

Tar Epoxy, Rubber, Mortar, Polypropylene, Polystryal, Polystyrenes, Polyester, Ebonite, Polyethylene, Teflon, etc.

Mounting

wall mounting, local

Display

2 Line LCD with backlight; 5 digits with decimal point for flow rate, 8 digits for Forward, Reverse & Net totalized values

Output

Analog

4-20mA or 0-20mA current output. Impedance 0∼1kW. Accuracy 0.1%.

Relay output

Over 20 source signal (no signal, reverse flow etc.)

Pulse Output

Frequency signal :1~9999 Hz

Input

Three analogue input

Three-wire PT100 resistor input (optional)

Other functions

Automatically record the totaliser data of the last 64 days / 64 months / 5 years;

The power-on time and corresponding flow rate of the last 64 power on and off events. Allow manual or automatic flow loss compensation

The instrument working status of the last 64 days

Communication

RS-232/RS485

Alarm

High/Low with buzzer

Protection

Transmitter

IP 65

Sensor

IP67/IP68 (optional)

Straight pipe section

In the upstream it must be beyond 10D, in the downstream it must be beyond 5D, in the upstream the length must be beyond 30D from the access of the pump. (D stands for pipe diameter)

Cable Length

Twisted Pair Line, standard length of 10m, can be extended to 500m (not recommended); Contact the manufacturer for longer cable requirement. RS-485 interface, transmission distance up to 1000m

Power Supply

Remote Type

90 ~ 260VAC 50/60 Hz; 9-28VDC

Compact Type

9-28VDC

Power Consumption

Less than 2W

Data Storage

Operation parameters and tantalization data are stored in EEPROM for more than 10 years

Engineer Unit

M3, Liter, US gallon, Imperial gallon, Million gallons, Cubic feet, US Barrels, Imperial barrels, Oil barrels

Time Units

Second, Minute, Hour, Day

Protocols

MODBUS, M-BUS, Fuji extended protocol and other factory protocol

Humidity

Main Unit: 85% RH

Remarks:  With a high strength carrying case suitable for normal and harsh environment

Model Selection
RBFM Ultrasonic Flowmeter Model Selection
RBFM   X
X X DNxx X X
X X X

Instrument Type

F Ultrasonic Flowmeter
H Ultrasonic Heat meter

Power supply
A 220VAC
D 24VDC
B Battery


Flow/Heat meter Type

BF Fixed type
   
H Handheld type
P Portable type
Flanged type
B Battery type

Transducer Type

SN S type(pipe size: 15-100mm, temp.: -30 to 90)
SH S type(pipe size: 15-100mm, temp.: -40 to 160)
SPMN S type with mounting frame only for RBFMH/P(pipe size: 15-100mm, temp.: -40 to 90)
SPMH S type with mounting frame only for RBFMH/P(pipe size: 15-100mm, temp.: -40 to 160)
MN M Type(pipe size: 50-700mm, temp.: -30 to 90))
MH M Type(pipe size: 50-700mm, temp.: -40 to 160))
MPMN M type with mounting frame only for RBFMH/P(pipe size: 50-300mm, temp.: -40 to 90)
MPMH M type with mounting frame only for RBFMH/P(pipe size: 50-300mm, temp.: -40 to 160)
RB-1 extended the mounting frame, for pipe:DN300-700mm, temp.: -40 to 90
RBH extended the mounting frame, for pipe:DN300-700mm, temp.: -40 to 90
LN L type(pipe size: 300-6000mm, temp.: -30 to 90)
LH L type(pipe size: 300-6000mm, temp.: -40 to 160)
I Insertion Type
IE Extended type
F Flanged type


DNxx Pipe size


Pipe material

C Carbon Steel
SS Stainless Steel
CI cast iron
F Fibreglass
P PVC
C cement pipe
X Others,  clarify

X Pressure(MPa)

Output
N NO
A 4-20mA
Pulse
R Relay
2 RS232
4 RS485
5 Datalogger

Input
NO
1 1*4-20mA
2 2*4-20mA
Applicants

RBBF Fixed Clamp-on Type Ultrasonic Flow Meter can be applied to a wide range of pipe flow measurements.

Applicable liquids include pure liquids as well as liquid with small quantity of tiny particles.

Examples are:

Water (hot water, chilled water, city water, sea water, waste water, etc.);

Sewage with small particle content;

Oil (crude oil, lubricating oil, diesel oil, fuel oil, etc.);

Chemicals (alcohol, acids, etc.);

Plant effluent;

Beverage, liquid food;

Ultra-pure liquids;

Solvents and other liquids 